Submersible Pump Station Electrical Riser Detail

Department: Public Utilities Posted: File: SubmersiblePumpStationElectricalRiserPg47.pdf

This PDF document may not meet current accessibility standards (WCAG 2.1 AA) and may not be fully usable with assistive technologies.

If you require access to the information in a more accessible format, please e-mail webstaff@johnstonnc.gov and we will provide an alternative version as soon as possible. A machine-generated text version is also available below.

We apologize for any inconvenience and appreciate your understanding as we work toward full accessibility compliance.

Open PDF in new tab Download Text version

If the document does not display above, download the PDF.

Text version (machine-generated from the PDF)
NOTES1, SERVICE TO BE 6OA, 3 PHASE, 4 WIRE, 460VWITH HIGH LEG,2, USE COPPER CONDUCTORS WISOO VOLTTHWN·THHN INSULATION,3, INSTALL GUY IF METER POLE IS IN EXCESS OF15 FROM SERVICE POLE4, CONTRACTOR SHALL FURNISH INSTALLMETER BASE ON SERVICE POLE5, CONTRACTOR SHALL INSTALL 120V SINGLEWP, RECEPTACLE IN VALVE VAULT FOR SUMPPUMP,RED ALARM LIGHT175 WAn HIGH PRESSURE SODIUM LUMINARE ON 24 ARM WI PHOTOCELL CONTROL MIN, S OFF GROUND PUMP CONTROL PANEL3 EA SEAL·OFFS WINON·HARDENING SEALINGMATERIALS,S, JUNCTION BOX WI SEAL OFFS 16166 NEMA 4 FOR PUMP POWER LEADS LIQUID LEVEL CABLES 4 WIRE LIGHTINGARRESTORSLACK SPAN TOUTILITY METER POLESEE NOTE #325 CLASS 5TREATED POLE3 POLE AUTOMATICTRANSFER SWITCHNEMA3RSTANDBYGENERATOR2 PVC CONDUITSFOR PUMP LEADSSEPARATE CONDUITFOR EACH PUMP 3 EA #12, 1 EA, #12 GD, 1 COND,YCONDUIT TO SUMP PUMP IN VALVE VAULTFOR TELEPHONERISER DIAGRAM NOT TO SCALEPAGESANITARY SEWERJOHNSTON COUNTYSTANDARD DETAILDepartment of Public Utilitiesp,o, Box 2263 Submersible PumpSmithfield, NC 27577 Station Electrical Riser Detail47
‹ Back to search