This detailed checklist outlines the common items evaluated by the Johnston County Fire Marshal's Office during a commercial fire inspection.

It is based on the North Carolina State Fire Prevention Code (NCFC), the NC Building Code, and relevant NFPA standards. Business owners and site managers can use this list to prepare for periodic commercial inspections or final Certificate of Occupancy (CO) sign-offs.

 

1. Means of Egress and Exits

  • Unobstructed Exit Paths: All hallways, corridors, stairwells, and exterior exit discharge paths must be clear of storage, furniture, boxes, or debris.
  • Exit Doors: Must open easily without special knowledge, keys, or keypads from the inside. Panic hardware must be installed on high-occupancy doors where required.
  • Fire Doors: Must self-close and latch automatically. Doors must never be wedged, propped open, or blocked.
  • Exit Signage: Exit signs must be continuously illuminated (main power and battery backup functioning).
  • Emergency Lighting: Must illuminate automatically during power failure. (Inspectors will press the test button to verify 30-second battery operation).
  • Occupancy Load Posting: Maximum occupant load signs must be clearly posted in assembly spaces (restaurants, bars, event venues).

 

2. Portable Fire Extinguishers (NFPA 10)

  • Accessibility: Extinguishers must be visible and unobstructed, mounted on wall hooks or in cabinets.
  • Mounting Height: Top of the extinguisher must be no more than 5 feet off the floor (for units under 40 lbs) and bottom at least 4 inches off the floor.
  • Travel Distance: Maximum 75-foot travel distance to an extinguisher throughout the building.
  • Inspection Tags: Must show an annual inspection tag completed by a licensed fire equipment technician.
  • Pressure and Pin: Pressure gauge indicator must be in the green operable zone with safety pins and tamper seals intact.
  • Class K Extinguishers: Required within 30 feet of commercial kitchen deep fryers or cooking lines.

 

3. Fire Alarm Systems (NFPA 72)

  • Alarm Panel Status: Main Fire Alarm Control Panel (FACP) must show a "Normal" status without active trouble, supervisory, or ground fault lights.
  • Clear Clearance: 36 inches of clear space must be maintained around alarm panels and manual pull stations.
  • Annual System Test: A copy of the current annual fire alarm inspection report must be uploaded via LIV Safe or available on site.
  • Pull Stations and Notification: Manual pull stations must be unobstructed, and strobes/horns must be intact and undamaged.

 

4. Fire Sprinkler and Standpipe Systems (NFPA 25)

  • Vertical Clearance: Minimum 18 inches of clearance below sprinkler heads (or 36 inches for high-piled rack storage) throughout the entire room.
  • Sprinkler Heads: Must be free of paint, dust, lint, or physical damage.
  • Riser Clearance and Valves: Sprinkler riser valves must be fully accessible, labeled, and locked/supervised in the open position.
  • Spare Heads and Wrench: A spare sprinkler head box with the correct types/temperatures and a sprinkler wrench must be located near the main riser.
  • Inspection Testing: Current annual sprinkler, backflow, and 5-year internal inspection reports must be on file.

 

5. Commercial Kitchen Suppression Systems (NFPA 96)

  • Hood System Certification: Fixed suppression systems must be inspected and certified every 6 months by a licensed technician with a current tag attached.
  • Hood and Duct Cleanliness: Exhaust hoods, baffles, grease filters, and ducts must be clean and free of grease buildup.
  • Nozzle Alignment: Hood discharge nozzles must point directly at the cooking appliances they protect.
  • Manual Pull and Fuel Shutoff: Pull station must be accessible in the path of egress, and fuel (gas/electric) must automatically shut off when the system trips.

 

6. Electrical Safety and Utilities

  • Electrical Panels: 36-inch clear space maintained in front of all electrical panels, sub-panels, and disconnects. Panel doors must close and have all open breaker slots covered.
  • Junction Boxes and Outlets: All junction boxes, light switches, and wall outlets must have secure cover plates installed. No exposed wiring.
  • Extension Cords: Extension cords are prohibited for permanent use. They may only be used for temporary power tools/equipment.
  • Power Strips: Surge protectors/power strips must plug directly into a wall outlet (no "daisy-chaining" power strips together).

 

7. Housekeeping and Storage Hazards

  • Combustible Storage: Storage must be kept organized and at least 2 feet below non-sprinklered ceilings (or 18 inches below sprinkler heads).
  • Mechanical and Boiler Rooms: Storage of combustible items (boxes, paper, mops, trash) inside mechanical, furnace, or electrical rooms is strictly prohibited.
  • Trash and Waste: Regular removal of trash, oily rags (must be in self-closing metal cans), and flammable waste.

 

8. Flammable and Hazardous Materials

  • Flammable Liquids: Stored in approved, labeled, fire-rated safety cabinets if quantities exceed code limits.
  • Compressed Gas Cylinders: All gas cylinders (nitrogen, CO2, oxygen, propane) must be individually secured to a wall or cart with chains or straps to prevent tipping.
  • Safety Data Sheets (SDS): SDS sheets must be accessible for chemical handling, and chemical storage areas must be labeled.

 

9. Address and Exterior Requirements

  • Building Address: Physical street address numbers must be clearly posted on the exterior of the building, visible from the street, and contrasting with the background (minimum 6 inches high for commercial).
  • Fire Department Connections (FDC): FDC connections must be clear of brush, landscaping, or parking, with brass or locking caps intact.
  • Fire Lanes: Exterior fire lanes must be painted, marked with signs, and completely free of parked vehicles.
  • Knox Box (Key Box): Knox Box must be mounted near the main entrance containing current master keys, elevator keys, and alarm codes for emergency responder entry.